Performance problems involving wood structural panels may occur during construction of the building or after the building has been completed and occupied. The most common problems are associated with dimensional changes of the installed panels after they have been exposed to moisture. These problems typically manifest themselves as panel buckling, warping, or twisting.
The equilibrium moisture content (EMC) of wood structural panels at the time of manufacture may be as low as 2-3 percent. The EMC of dry, protected, wood building products installed in occupied buildings can vary from 6-12 percent, depending on regional environmental conditions. Since wood materials expand as their moisture content increases, it is recommended that the panels be acclimated to their surroundings prior to installation. Care must also be taken during installation to allow for expansion. This is especially important if the panels will be exposed to wet weather conditions during the construction process. The performance standards for wood structural panel products provide limitations as to the amount of linear expansion panels are allowed to exhibit when tested under extreme exposure conditions. Most wood structural panel manufacturers also recommend a minimum 1/8-inch (3-mm) space be provided around the perimeter of the panels to allow for expansion. Field investigations involving buckled, warped and/or twisted panels typically reveal that the recommended spacing was not provided (see Figure 1). These investigations also often indicate that the size and spacing of the fasteners used to attach the panels to the framing was insufficient.
Panel expansion can also occur after the building is occupied. In cold weather climates, excessive expansion of roof panels is typically the result of poor attic ventilation, stemming from improper design or poor construction practices. Building codes in the United States and Canada offer prescriptive ventilation requirements for residential construction, but occasionally these requirements are not properly implemented.
Poor building practices are unfortunately all too common, and include obstruction of soffit and roof ridge vents or the discharge of ventilation ducts from the interior of the building directly into the attic space (see Figure 2). The result of each of these poor practices is an increased moisture load in the attic space, which creates a moisture gradient within the panels and uneven panel expansion. If the panels are not spaced and/or fastened properly and are exposed to excessive moisture from any of these examples, buckling or warping is usually the result (see Figure 3).
Panels that buckle, warp or twist after installation are usually not defective and typically do not need to be replaced. If the panels were installed too tight (i.e., without the recommended 1/8-inch space at panel ends and edges), spacing can be added by cutting a kerf at the panel joints with a circular saw (see Figure 4). These panels can generally be brought back into plane by securely attaching the deformed portion of the panel to dimension lumber blocking and attaching the blocking to adjacent structural framing members (see Figure 5). Before the panels can be repaired, the root cause of the deformation must be determined and fixed. Additional ventilation or proper ventilation may be needed. Care must be taken not to cut too deep and cause damage to the support framing.
An example (see Figure 6) of repair recommendation for the unsupported and buckled roof sheathing panels is presented in the drawing on the final page.
Figure 1
Buckling of the plywood between supports due to wetting on the top surface and inadequate panel spacing during installation.
Figure 2
Top left: Ventilation duct from interior of building terminates in attic space instead of directly to outside of the building.
Top right: Space in panels for continuous ridge vent has been covered by roofing underlayment and shingles.
Bottom: Soffit intake ventilation has been covered by insulation and lumber blocking.
Figure 3
Buckling and ridging of the roof sheathing panels due to ventilation problems.
Figure 4
Inadequate spacing between the adjoining panels; adding space between the panels by cutting a kerf at the panel joints with circular saw (photo insert).
Figure 5
Simple and effective repair for buckled, warped or twisted roof sheathing panels is to securely attach the deformed portion of the sheathing to dimension lumber blocking and attach the blocking to adjacent support framing.
Figure 6
Repair recommendation for the unsupported and buckled roof sheathing panels.